Substations transform electric energy to different voltage levels in the public power supply grid for both households and rail transport. Depending on the high voltage, the transformation takes place in either outdoor (110 - 400 kV) or indoor stations (6 - 110 kV). Substations normally consist of power transformers, switchboards as well as measurement and control systems. Transformer stations without power transformers are called load balancers. Due to the high automation, substations can be operated remote-controlled.
The given nominal voltage is the target voltage to which another higher voltage has been stepped down to.
Measurand | Value | Feature | Remarks |
---|---|---|---|
magnetic flux density | 9.4 µT (mean, measured) | Slovenia | average value out of 17 measurement points in an apartment above a 10 kV transformer substation (24 h measurement) [1] |
magnetic flux density | 11.4 µT (maximum, measured) | Slovenia | maximum value out of 17 measurement points in an apartment above a 10 kV transformer substation (on the spot measurement) [1] |
magnetic flux density | 15.6 µT (maximum, measured) | Slovenia | maximum value out of 17 measurement points in an apartment above a 10 kV transformer substation (24 h measurement) [1] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
electric field strength | 0.09–0.4 kV/m (measured) | Finland | during work near the power transformer [2] |
electric field strength | 0.6 kV/m (maximum, measured) | Finland | during the maintenance of a circuit breaker from below the service platform [3] |
electric field strength | 2.4–10.6 kV/m (maximum, measured) | Finland | during the maintenance of a circuit breaker on ground floor [4] |
electric field strength | 2.8–16.6 kV/m (maximum, measured) | Finland | during maintenance from the service platform [2] |
electric field strength | 3.6 kV/m (maximum, measured) | Finland | during the inspection of a distribution cabinet on the ground [3] |
electric field strength | 5–7.4 kV/m (maximum, measured) | Finland | during maintenance or inspection walk within the substation [2] |
electric field strength | 6.1 kV/m (maximum, measured) | Finland | while walking in the substation [3] |
electric field strength | 7.4–15.7 kV/m (maximum, measured) | Finland | during the maintenance of a circuit breaker on the service platform [4] |
electric field strength | 15.5 kV/m (maximum, measured) | Finland | during the maintenance of circuit breakers from a service platfrom [3] |
current density | 0.9–1.8 mA/m² (maximum, simulated) | Finland | maximum induced current densitiy in the neck of worker during the maintenance of a cirucuit breaker on the service platform [4] |
current density | 1–1.4 mA/m² (maximum, simulated) | Finland | maximum induced current density in the neck of a worker during the maintenance of a circuit breaker at ground floor [4] |
current density | 1.3 mA/m² (maximum, simulated) | Finland | maximum induced current densitiy in the neck of a worker during the maintenance of a disconnector on ground floor [4] |
magnetic flux density | 0.1 µT (measured) | Finland | at a distance of 30 m to the fence [5] |
magnetic flux density | 0.2 µT (measured) | Finland | at a distance of 20 m to the fence [5] |
magnetic flux density | 1.5 µT (measured) | Finland | while working near the capacitors on the ground [3] |
magnetic flux density | 2 µT (measured) | Finland | gas-insulated: inside the cable room at a distance of 2 m to the cables [6] |
magnetic flux density | 3.9 µT (measured) | Finland | gas-insulated: on top of the switch gear [6] |
magnetic flux density | 7.9 µT (measured) | Finland | gas-insulated: outside at a height of 170 cm near power transformers [6] |
magnetic flux density | 9 µT (measured) | Finland | gas-insulated: inside the cable room at a distance of 80 cm to a cable [6] |
magnetic flux density | 10.5 µT (measured) | Finland | while walking in the substation [3] |
magnetic flux density | 27 µT (measured) | Finland | gas-insulated: in the cable room at a distance of 40 cm to a cable [6] |
magnetic flux density | 28.6 µT (mean, measured) | - | out of 28 different tasks at various locations within the substation [3] |
magnetic flux density | 40.3 µT (mean, measured) | Finland | while working near the power transformer [3] |
magnetic flux density | 100 µT (measured) | Finland | gas-insulated: in the cable room at a distance of 20 cm to a cable [6] |
magnetic flux density | 178 µT (measured) | Finland | gas-insulated: in the cableroom, directly at a cable [6] |
magnetic flux density | 195.5 µT (mean, measured) | Finland | while working near the fence of a reactor (20 kV) [3] |
magnetic flux density | 204 µT (measured) | Finland | gas-insulated: outside at a height of 170 cm near the cables of a power transformer [6] |
magnetic flux density | 250 µT (measured) | Finland | gas-insulated: inside the cable room, between calbes [6] |
magnetic flux density | 420 µT (maximum, measured) | Finland | at the busbars [5] |
magnetic flux density | 559.8 µT (mean, measured) | Finland | while walking near the reactor cables [3] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
electric field strength | 41.186–140.9 µV/m (calculated) | Turkey | induced electric field in a human body beneath the busbars [8] |
electric field strength | 82.372 µV/m–190.75 mV/m (calculated) | Turkey | induced electric field in a human body in front of the circuit breakers [8] |
current density | 8.237–28.18 µA/m² (calculated) | Turkey | induced electric current in a human body beneath the busbars [8] |
current density | 16.474–38.15 µA/m² (calculated) | Turkey | induced current densitiy in a human body in front of the circuit breakers [8] |
magnetic flux density | 1.9–6.5 µT (measured) | Turkey | beneath the busbars [8] |
magnetic flux density | 3.8–16.474 µT (measured) | Turkey | in front of the circuit breaker [8] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
magnetic flux density | 4.9 µT (measured) | Japan | beneath the departing power lines at the fence [9] |
magnetic flux density | 6.85 µT (measured) | Japan | beneath the busbars [9] |
magnetic flux density | 7.34 µT (measured) | Japan | between lightning arrester and current transformator [9] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
electric field strength | 1.2–5 kV/m (measured) | Italy | at a height of 1.5 m above ground at the disconnector busbars [10] |
electric field strength | 3–4.6 kV/m (min-max value, measured) | Italy | at a height of 1.5 m above ground at the circuit breakers [10] |
magnetic flux density | 4–12.5 µT (measured) | Italy | at a height of 1.5 m above ground at the disconnector busbars [10] |
magnetic flux density | 7–10.8 µT (measured) | Italy | at a height of 1.5 m above ground at the circuit breakers [10] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
electric field strength | 1.15 V/m (maximum, measured) | Iran | at a distance of 50 m [11] |
electric field strength | 0.681 kV/m (mean, measured) | Iran | out of 607 measuring points at 3 different substations [7] |
electric field strength | 1,647 V/m (maximum, measured) | Iran | within the substation [11] |
magnetic flux density | 0.16–2.28 µT (mean, measured) | Iran | in the battery room [12] |
magnetic flux density | 0.2–0.69 µT (mean, measured) | Iran | in the control room [12] |
magnetic flux density | 0.749 µT (mean, measured) | Iran | out of 607 measuring points at 3 different substations [7] |
magnetic flux density | 1.1–9.15 µT (mean, measured) | Iran | in the switchgear [12] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
electric field strength | 23.4 µV/m (maximum, calculated) | Turkey | induced electric field in a human body beneath the busbars [13] |
current density | 4.68 µA/m² (maximum, calculated) | Turkey | induced current density in a human body beneath the busbars [13] |
magnetic flux density | 3.3 µT (measured) | Turkey | at a height of 1.8 m above ground next to the transformator [13] |
magnetic flux density | 5.4 µT (maximum, measured) | Turkey | beneath the busbars [13] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
electric field strength | 25 mV/m (measured) | Japan | induced electric field in the neck of a worker during maintenace of circuit breakers or resp. disconnectors; height: 1.52 m; distance: 0.5 m [14] |
electric field strength | 0.78 V/m (minimum, measured) | Iran | at a distance of 50 m [11] |
electric field strength | 0.838 kV/m (mean, measured) | Iran | out of 155 measuring sights at one substation [7] |
electric field strength | 1.521 kV/m (maximum, measured) | Iran | inside the substation [11] |
electric field strength | 11.2–11.9 kV/m (mean, measured) | Finland | on the service platform [15] |
electric field strength | 12.8 kV/m (measured) | Japan | during maintenance of circuit breakers or resp. disconnectors at a height of 1.7 m and a distance of 0.5 m [14] |
electric field strength | 15.5 kV/m (maximum, measured) | Finland | during the maintenance of circuit breakers at ground level [3] |
electric field strength | 15.6 kV/m (measured) | Japan | during maintenance of circuit breakers or resp. disconnectors at a height of 1.7 m and a distance of 0.3 m [14] |
electric field strength | 18.4–24.5 kV/m (mean, measured) | Finland | at a height of 1.7 m on the service platform [15] |
electric field strength | 18.5 kV/m (maximum, measured) | Finland | during an inspection from the maintenance platform [3] |
electric field strength | 21 kV/m (measured) | Japan | during maintenance of circuit breakers or resp. disconnectors at a height of 1.7 m and a distance of 0.1 m [14] |
electric field strength | 25.7 kV/m (mean, measured) | Finland | during the inspection of the busbars [16] |
electric field strength | 36.4 kV/m (maximum, measured) | Finland | at circuit breakers [15] |
electric field strength | 43.5 kV/m (maximum, measured) | Finland | during the inspection of busbars using a ladder [3] |
electric field strength | 43.5 kV/m (maximum, measured) | Finland | during the inspection of the busbars [16] |
electric field strength | 47 kV/m (maximum, measured) | Finland | during the inspection of the current transformer from a ladder [3] |
electric field strength | 47 kV/m (maximum, measured) | Finland | during the inspection of the current transformator from a ladder [16] |
electric field strength | 59 kV/m (measured) | Sweden | at a distance of 6 m and a height of 1.8 m [17] |
electric field strength | 65 kV/m (measured) | Sweden | at a distance of 1 m and a height of 1.8 m [17] |
current density | 1.5 mA/m² (mean, simulated) | Finland | induced current density in the neck of a worker during the maintenance of disconnectors [16] |
current density | 2.2 mA/m² (mean, calculated) | Finland | during maintenance of circuit breakers from the service platform in the neck [15] |
current density | 4.5 mA/m² (mean, calculated) | Finland | induced current density in the neck of a worker during inspection of the current transformator from a ladder [16] |
current density | 5.7 mA/m² (maximum, calculated) | Finland | during maintenance of circuit breakers from the service platform in the neck [15] |
current density | 6.4 mA/m² (maximum, simulated) | Finland | induced current density in the neck of a worker during inspection of the current transformator from a ladder [16] |
magnetic flux density | 0.751 µT (mean, measured) | Iran | out of 155 measuring points at one substation [7] |
Measurand | Value | Feature | Remarks |
---|---|---|---|
magnetic flux density | 0.26 µT (maximum, measured) | Japan | at a distance of 7.5 m to the underground cables burid at a depth of 0.95 m [9] |
magnetic flux density | 2.15 µT (maximum, measured) | Japan | value beneath the busbars [9] |
magnetic flux density | 4.84 µT (maximum, measured) | Japan | between the circuit breakers [9] |
This website uses cookies to provide you the best browsing experience. By continuing to use this website you accept our use of cookies.